Opt-i-Mizer EOM-B
EOM-B
is
a 3 phase 4 wire advanced microprocessor controlled,
energy
saving Basic controller.
Specifically designed for use with HID light units such as:
High Pressure Sodium, Metal Halide, Mercury Vapor,
and Fluorescent Lamps.
Features
- Totally self-contained
microprocessor control.
- Built-in programmable
timer, under and over voltage protection.
- Requires no changes to
customers existing lighting infrastructure.
- Provides up to 30%
reduction in Energy Cost.
- Built-in Manual Bypass
facility.
- No Harmonic Distortion
with pure Sine Wave Output.
- More than 98.5% Efficient.
- Built-in winding over
temperature trip (thermo element switch)
- Increases lamp life by up
to 300%.
- Modular design with
minimal maintenance.
- CE and IEC approved to
60439-1
- Approved by OSRAM and
Philips
Range
- EOM-B-30A 400V 3ph. 4W
30A per phase
Un-enclosed
Dimensions: 300mm W x 610mm H x 270mm D
- EOM-B-50A 400V 3ph. 4W
50A per phase
Un-enclosed
Dimensions: 300mm W x 610mm H x 270mm D
- EOM-B-80A 400V 3ph. 4W
80A per phase
Un-enclosed
Dimensions: 300mm W x 610mm H x 270mm D
- EOM-B-100A 400V 3ph. 4W
100A per phase
Un-enclosed
Dimensions: 388mm W x 711mm H x 291mm D
- EOM-B-125A 400V 3ph. 4W
125A per phase
Un-enclosed
Dimensions: 388mm W x 711mm H x 291mm D
- EOM-B-160A 400V 3ph. 4W
160A per phase
Un-enclosed
Dimensions: 388mm W x 711mm H x 291mm D
- EOM-B-210A 400V 3ph. 4W
220A per phase
Un-enclosed
Dimensions: 630mm W x 711mm H x 350mm D
Technical
Specification
- Input voltage: 400V (3x230VAC)
- Output voltage: Input voltage less 25V (opt.
22V or 20V or 15V)
- Frequency: 50-60Hz
- Energy saving: Above 20% (depend on voltage
reduction)
- Power Range: (Capacity) 3 x 30A up to 3 x
220A
- Control Voltage: 230VAC+15%
- Min input voltage protection: 170-230V
- Fault indicator Lamp: LEDs
- Insulation: 2.5kV
- Ambient Temp: -20ºC to +50ºC
- Operation mode: Under input Voltage protection.
- By Pass Switch: manual
- Standard CE, EN60439-1 (safety
approval)
Method of
Operation
All EOM-B
units are designed for installation within the contactor supply cable
to the distribution boards of the lighting system.
(Input contactor
should be installed before the controller)
The EOM-B
is usually mounted next to, as far as is practicable, the lighting
distribution board.
Protection
The supply and
load are protected by suitably rated Miniature Circuit Breakers.
The EOM-B
is equipped with thermal trips on the windings of the coils that will
trip the supply on over temperature alarm.
Under and over
voltage is a preset parameter of the microprocessor and will activate
an alarm and in the case of under input voltage will prevent the unit
from going into ‘Energy Saving’ mode.
The EOM-B
is fitted with a Manual Bypass Switch.
OPERATING
PRINCIPLE
After the power is
supplied to the controller and if the ‘ON’ command exists,
the controller supplies full voltage to the system.
Providing the
‘Energy Saving’ contact is enabled, the programmed delay
time will commence, which is fixed at 6 minutes.
After the timer
expires the EOM-B is in Energy Saving’ mode and the output
voltage is reduced by approximately 10% (e.g. if the input voltage is
230V, the output voltage will be 205V).
In the case of
power failure, after the power returns (restart), and all the control
signals (‘ON’ & ‘Energy Saving’) are still
present, the controller provides full voltage to the system and energy
saving will begins after the time delay as mentioned above.
If, during energy
saving mode, it becomes necessary to restart some or all lamps, this
can be achieved by opening the connection to terminals 3 & 4
(disable ‘Energy Saving’ mode).
The unit will now
supply full voltage until the ‘Energy Saving’ mode is
enabled and the timer has elapsed.